Installation And Start-Up
3-21
Copyright
2001 Phone: (614) 771-2718 RE-4500
Vanner Inc. FAX: 614-771-4904 Owners Manual
4282 Reynolds Dr. www.vanner.com Rev 01e
Hilliard Ohio 43026 RE-Installation_Manual_Rev01e 910157-A
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
required, cut a slot to connect the two holes to prevent
heating of the ferrous metal.
4.
If passing through any sort of holes, make certain that
strain reliefs are used to avoid cutting or abrasion of
insulation over time.
5.
Proper DC cable size is critical for the performance and
safe operation of the inverter system. It is required by
Vanner that the installer use 4/0 AWG wire to minimize
losses to less than ½ volt over the length of the cable. This
wire needs to be rated for 90ºC.
6.
DC cables should be as short as possible to minimize
losses.
7.
The DC power connections to the inverter require that
5/16” Dia. ring terminals be used for connection to the
inverter unless the optional mechanical compression blocks
(Vanner P/N D08421) are used. A list of suitable terminals
as well as the tools required to crimp them are shown in
Table 3-1: Ring Terminals for 4/0 DC Cables.
Molex Part Number ModelSize Crimping Tool Part Numbers
L-395-56
L-995-56
5/16" DIA.
Versacrimp
Nylacrimp
DLHH, PPDLH,SKT-840*
*This tool is for crimping Versacrimp style terminals only.
UL Listed Ring Terminals for 4/0 DC Cables
Table 3-1: Ring Terminals for 4/0 DC Cables