Appendix C: Settings
D-1
Copyright
2001 Phone: (614) 771-2718 RE-4500
Vanner Inc. FAX: 614-771-4904 Owners Manual
4282 Reynolds Dr. www.vanner.com Rev 01e
Hilliard Ohio 43026 RE-Installation_Manual_Rev01e 910157-A
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
Appendix C: Settings
Alarm Listing
Alarm Display Description
BATTERY LOW
Battery Low Warning
BATT. TOO HIGH
Battery High Shutdown
BATT. TOO LOW
Battery Low Shutdown
CURRENT LIMIT
At the Inverter current limit
BROWNED OUT
Shutdown because the inverter output voltage has been too low for
too long
BRICK FAULT
Power stage shutdown
XFRMR OVERHEAT
Transformer overheated
BRICK OVERHEAT
The power stage overheated
BATT. OVERHEAT
The batteries overheated. Note: Battery temperature compensation
must be ON
SYS. OVERHEAT
The internal temperature sensor reported >60 degrees C.
SURGING...
The load is greater than the inverter current limit; not limiting yet.
BAD GRID FREQ.
The utility or generator frequency is bad. (The voltage might be
OK).
PHASE MISMATCH
Line 1 and Line 2 voltages don't agree.
NO PHASELOCK
The transfer relay has not yet energized. The voltage and
frequency of the grid might be OK.
GRID L1-N BAD
Bad phase voltages
GRID L2-N BAD
Bad phase voltages
OPEN FUSE
The small inverter has blown its fuse
SOFTWARE FAULT
Software error - Checksum
BATTERY DEAD
Battery Low Shutdown, no charging. < 1/2 Battery Low Shutdown
value.
INVERTING
Normal
INVERTING-SMAL
Inverting “low power” with small inverter
Vedere la pagina 82